Applies to part number: E9X-RUV, E9X-DUV-..., 


To restore factory default settings for any reason, use the following sequence:


  1. Activate "Advanced Setup" - Hold the MENU button (20 seconds) until the LED blinks AMBER and relay is not clicking (at 5 seconds, relay will click - keep holding button, at 15 seconds LED blinks 1 AMBER blink pattern, then a pause - release button)
  2. Activate "Clear Mode" - Press the SELECT button 4 times, confirm that the LED is blinking a 5 blink Amber pattern, with a pause. (If the LED is not blinking a 5 blink Amber pattern, press the SELECT button to cycle through the modes until the 5 blink "Clear Mode" pattern is active.)
  3. Restore Factory defaults - Hold the SELECT button (20 seconds) until the LED turns GREEN (Status LED starts on Amber 5 blink pattern, at 5 seconds it pauses on Red, then resumes Amber blinking. At 20 seconds, it should pause again on Red, then turn solid GREEN)
  4. Success - Factory defaults have been restored.