Firmware version 4.2.2.x:
- Invert output may be turned on inadvertently by the Scan & Link Gateway. Affects: DUV, DUV-FX, RUV products. There are two workarounds options:
- Option A
- Turn invert outputs back off using the push button menus as described in the installation manual. 6 Amber, 5 Green, 1 Red blink.
- Option B
- In the scan and link app, select the controller in the "Devices" view instead of the "Groups" view.
- Select the gear icon, then config options
- Import the device settings, then find invert output and make sure it is set to relay asserted (closed)
- Press the 3 dot menu next to invert output and select resend
- Option A