Firmware version 4.2.2.x:

  • Invert output may be turned on inadvertently by the Scan & Link Gateway. Affects: DUV, DUV-FX, RUV products. There are two workarounds options:
    • Option A
      • Turn invert outputs back off using the push button menus as described in the installation manual. 6 Amber, 5 Green, 1 Red blink.
    • Option B
      • In the scan and link app, select the controller in the "Devices" view instead of the "Groups" view.
      • Select the gear icon, then config options
      • Import the device settings, then find invert output and make sure it is set to relay asserted (closed)
      • Press the 3 dot menu next to invert output and select resend